Function Details
ESIE15-13C
56
Function and Control
Control logic of the Free Cooling
DT-fc: Indoor T - Outdoor T
DT-rs: Room T - Setpoint T
X: To increase the free cooling start temperature
Y: The minimum required DT-fc to start the free cooling
ON
DT-fc
Y/2
0
DT-rs ≥ 2+X
Thermo off
Y & Thermo on + X
OFF
Free cooling