Troubleshooting by Remote Controller
ESIE15-13C
154
Service Diagnosis
4.22 Thermistor System Abnormality
Remote
Controller
Display
H9
,
J3
,
J5
,
J6
,
J7
,
J8
Applicable
Models
RZQG
Method of Error
Detection
The error is detected according to the temperature detected by each individual thermistor.
Error Decision
Conditions
When thermistor is disconnected or short circuited during operation
Supposed
Causes
Defective thermistor
Defective connection of connector
Defective outdoor unit PCB (A1P)
Troubleshooting
Error Code
Defective Thermistor
Symbol
H9
Outdoor air thermistor
R1T
J3
Discharge pipe thermistor
R2T
J5
Suction pipe thermistor
R3T
J6
Heat exchanger thermistor
R4T
J7
Intermediate heat exchanger thermistor
R5T
J8
Liquid pipe thermistor
R6T
Connect correctly.
Is it normal?
Replace the outdoor unit PCB
(A1P).
NO
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Remove thermistor from outdoor unit
PCB, then measure the resistance
using a tester.
Check connectors for connection.
YES
Replace the thermistor.
Is it normal?
NO
YES
CHECK 1
CHECK 1
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...