ESIE15-13C
Troubleshooting by Remote Controller
Service Diagnosis
149
Refer to P.185.
Refer to P.192.
Actually, it is in wet operation.
Restart operation.
Replace the outdoor unit PCB
(A1P).
YES
A
External factor (Noise, etc.)
NO
CHECK 1
Refer to
to eliminate the
causes of wet operation.
Error is displayed again?
CHECK 7
YES
YES
Replace the pressure sensor.
NO
Replace the defective
thermistor.
NO
Are
the characteristics
of each thermistor normal?
Are
the pressure sensor
characteristics normal?
CHECK 1
CHECK 7
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...