Si33-105
Troubleshooting
Troubleshooting R407C PLUS Series Heat Recovery System
173
3.17 Outdoor Unit:
Malfunction of Moving Part of Electronic
Expansion Valve (Y1E)
Remote
Controller
Display
E9
Supposed
Causes
!
Defect of moving part of electronic expansion valve
!
Defect of outdoor unit PC board (A1P)
!
Defect of connecting cable
Troubleshooting
"
1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
"
: Continuity Approx. 300
Ω
#
: Continuity Approx. 150
Ω
×: No continuity
(VF043)
Electronic
expansion valve is
connected to X14A of outdoor
unit PC board
(A1P).
Normal
when coil check (
H
1)
of the moving part of the
electronic expansion
valve is checked.
The connecting cable
is short-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board A1P.
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
After connecting, turn the power
off and then back on again.
YES
YES
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
"
×
#
×
2. Yellow
×
"
×
#
3. Orange
×
#
×
4. Blue
×
#
5. Red
×
6. Brown
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...