Troubleshooting
Si33-105
160
Troubleshooting R407C PLUS Series Heat Recovery System
3.4
Indoor Unit:
Fan Motor (M1F) Lock, Overload
Remote
Controller
Display
A6
Supposed
Causes
!
Fan motor lock
!
Disconnected or faulty wiring between fan motor and PC board
Troubleshooting
Connect the wiring and turn on
again.
Fix the wiring and turn on again.
YES
NO
NO
NO
YES
YES
Replace the indoor unit PC board.
Replace the fan motor.
Is the
wiring from the
fan motor securely
connected to X4A and X5A
on the indoor unit
PC board?
Wiring
between the
indoor unit PC board
and fan motor is
disconnected.
Does the fan motor run?
(VF031)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.