Outline of Control (Outdoor Unit) < Symbols using in this manual >
Si33-105
68
Function R407C PLUS Series Heat Recovery System
3.4.2 Motorized Valve PI Control (Heating)
Controls the motorized valves (EV1, EV2, EV3) to maintain the outlet superheated degree (SH)
of the outdoor heat exchanger (evaporator) at constant during heating operation.
SH = Th7 – Te
Te: Low pressure equivalent saturation temperature (°C)
Th7: Accumulator outlet temperature (°C)
Superheated degree target value (SHS)
!
Initial value at the start of motorized valve control: SHS = 5 °C
!
When Th7 – Te < 5: SHS (new) = SHS (current) + 1
However, when Th7 – Te < 5 and DSHi < 30: SHS = 7 °C (fixed)
!
When Th7 – Te > 10: SHS (new) = SHS (current) – 1
DSHi: Inverter discharge pipe superheat
3.4.3
Heat Exchanger PI Control (Heating & Simultaneous Cooling/Heating
Operation Mode)
In heating and simultaneous cooling/heating operation, conducts heat exchanger PI control,
switches the operation mode through 3 of 4-way valves, and adjusts the capacity by controlling
3 off electronic expansion valves, outdoor fan, auxiliary heat exchanger, and pressurizing valve.
16 to 20 HP
Note:
GR/SH control: Imaginary refrigerant circulation amount/Super heat degree control
step
No.
Heat exchanger 1
Heat exchanger 2
Pressurizing
valve
Y5S
20S1
Heat
exchanger
mode
20E1
Aux.
condensor
Fan
(MF11+MF12)
20S2
Heat
exchanger
mode
20E2
Fan
(MF3+MF4)
b
OFF
cond
0pls
OFF
H+OFF
OFF
cond
2000pls
ON+ON
OFF
a
OFF
cond
0pls
OFF
L+OFF
OFF
cond
2000pls
ON+ON
OFF
0
ON
evp
0pls
ON
H+ON
OFF
cond
2000pls
ON+ON
OFF
1
ON
evp
0pls
OFF
H+ON
OFF
cond
2000pls
ON+ON
OFF
2
ON
evp
0pls
OFF
H+ON
OFF
cond
1000pls
ON+ON
OFF
3
ON
evp
0pls
OFF
H+ON
OFF
cond
700pls
ON+ON
ON
4
ON
evp
0pls
OFF
H+ON
OFF
cond
500pls(PI)
ON+ON
ON
5
ON
evp
0pls
ON
H+ON
OFF
cond
2000pls
ON+OFF
OFF
6
ON
evp
0pls
ON
H+ON
OFF
cond
1000pls
ON+OFF
OFF
7
ON
evp
0pls
ON
H+ON
OFF
cond
700pls
ON+OFF
ON
8
ON
evp
0pls
ON
H+ON
OFF
cond
500pls(PI)
ON+OFF
ON
9
ON
evp
0pls
OFF
H+ON
OFF
cond
2000pls
ON+OFF
OFF
10
ON
evp
0pls
OFF
H+ON
OFF
cond
1000pls
ON+OFF
OFF
11
ON
evp
0pls
OFF
H+ON
OFF
cond
700pls
ON+OFF
ON
12
ON
evp
0pls
OFF
H+ON
OFF
cond
500pls(PI)
ON+OFF
ON
13
ON
evp
GR/SH
control
OFF
H+ON
OFF
cond
2000pls
ON+OFF
OFF
14
ON
evp
GR/SH
control
OFF
H+ON
OFF
cond
1000pls
ON+OFF
OFF
15
ON
evp
GR/SH
control
OFF
H+ON
OFF
cond
700pls
ON+OFF
ON
16
ON
evp
GR/SH
control
OFF
H+ON
OFF
cond
500pls(PI)
ON+OFF
ON
23
ON
evp
GR/SH
control
OFF
H+ON
OFF
cond
1000pls
OFF+OFF OFF
24
ON
evp
GR/SH
control
OFF
H+ON
ON
evp
0pls
ON+ON
OFF
25
ON
evp
GR/SH
control
OFF
H+ON
ON
evp
SH
control
ON+ON
OFF
500pls(PI)
: Pc control
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...