Si33-105
Outline of Control (Outdoor Unit) < Symbols using in this manual >
Function R407C PLUS Series Heat Recovery System
77
3.5.3 Discharge Pipe Temperature Control
Controls the liquid injection and operating frequency to prevent abnormal increase of discharge
pipe temperature and compressor internal temperature.
Liquid Injection Control
Inverter compressor
!
Opens SVTi (Y3S) (solenoid valve for inverter compressor liquid injection) for 3
minutes after software startup.
[Cooling and Simultaneous cooling / heating operation]
DSHi: Inverter compressor discharge pipe superheated degree
= Tdi (Th3-1) - (HP equivalent saturation temperature)
Tdi: Inverter compressor discharge pipe temperature (Th3-1)
[Heating]
[Preparing Oil return and defrosting operation (1 min before operation start)]
!
SVTi is ON during oil return and defrost operation.
[Oil return operation/defrosting operation]
!
SVTi (Y3S) is OFF at any case when inverter compressor stops.
Normal operation
SVTi : ON
DSHi
≥
40˚C
Lp<0MPa
DSHi<15˚C
DSHi>15˚C
(V0826)
OR
OR
&
&
DSHi<25˚C
Lp>0MPa
10min elapsed
Normal operation
SVTi : ON
•
Tdi
≥
100˚C
•
LP<0.05MPa
•
(HP+0.10) / (LP+0.10) >8
•
DSHi>35˚C
•
DSHi<20˚C
•
Tdi<90˚C
•
LP>0.07MPa
•
2 min elapsed
(V0827)
OR
OR
&
&
Preparing oil return
and defrosting
SVTi : ON
DSHi
≥
15˚C
Start oil return
& Defrost operation
(V0828)
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...