Outline of Control (Outdoor Unit) < Symbols using in this manual >
Si33-105
66
Function R407C PLUS Series Heat Recovery System
Compressor Operation Steps
The operating frequency changes in the following steps.
!
RSEYP16K~20K
!
RSEYP24K~30K
NO.
Frequency
NO.
Frequency
INV
STD
INV
STD1
STD2
1
29Hz
OFF
1
29Hz
OFF
OFF
2
31Hz
OFF
2
31Hz
OFF
OFF
3
33Hz
OFF
3
33Hz
OFF
OFF
4
35Hz
OFF
4
35Hz
OFF
OFF
5
37Hz
OFF
5
37Hz
OFF
OFF
6
39Hz
OFF
6
39Hz
OFF
OFF
7
41Hz
OFF
7
41Hz
OFF
OFF
8
43Hz
OFF
8
43Hz
OFF
OFF
9
46Hz
OFF
9
46Hz
OFF
OFF
10
48Hz
OFF
10
48Hz
OFF
OFF
11
52Hz
OFF
11
52Hz
OFF
OFF
12
55Hz
OFF
12
55Hz
OFF
OFF
13
58Hz
OFF
13
58Hz
OFF
OFF
14
62Hz
OFF
14
62Hz
OFF
OFF
15
64Hz
OFF
15
64Hz
OFF
OFF
16
67Hz
OFF
16
67Hz
OFF
OFF
17
71Hz
OFF
17
71Hz
OFF
OFF
18
75Hz
OFF
18
75Hz
OFF
OFF
19
37Hz
ON
19
37Hz
ON
OFF
20
41Hz
ON
20
41Hz
ON
OFF
21
46Hz
ON
21
46Hz
ON
OFF
22
52Hz
ON
22
52Hz
ON
OFF
23
58Hz
ON
23
58Hz
ON
OFF
24
64Hz
ON
24
64Hz
ON
OFF
25
71Hz
ON
25
71Hz
ON
OFF
26
79Hz
ON
16 HP upper
limit
26
41Hz
ON
ON
27
87Hz
ON
27
52Hz
ON
ON
28
95Hz
ON
18, 20 HP
upper limit
28
64Hz
ON
ON
29
79Hz
ON
ON
24, 26 HP
upper limit
30
87Hz
ON
ON
31
95Hz
ON
ON
28, 30 HP
upper limit
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...