Test Operation R407C PLUS Series Heat Recovery System
1.11 Backup and Emergency Operation
1.11.1
Backup Operation
:
When a constant speed type compressor malfunctions due to OC actuation, if you restart
operation by remote controller after the unit stops, you can continue to operate the system
without the faulty constant speed type compressor.
The system can run by backup operation for up to 3 hours of total indoor unit operating time.
When 3 hours is exceeded and the malfunction still remains, the system once again stops due
to malfunction. If the malfunction returns to normal, the system continues to operate as is.
Backup
Operation
Control Flow
After the system briefly stops due malfunction in order to call attention to the problem, backup
operation is started by remote controller.
For the reason described above, after about 3 hours of backup operation, the system again
carries out malfunction detection, and the system once again stops due to malfunction if an
error is detected.
Note:
1. < For 2-compressor system >
!
When the STD compressor OC operates, the operation continues using only the inverter
compressor based on remote control reset. (for 3 hours only)
< For 3-compressor system >
!
When OC operates again immediately after a backup operation (within 5 minutes after STD
compressor startup), STD1 and STD2 are switched and operation is retried.
!
If OC activates again, only the inverter compressor is used for the operation.
!
(In any case, the backup operation ends after 3 hours.)
!
The compressor in which OC is activated is prohibited to operate until power reset is
conducted for a restart.
Malfunction occurs.
(MF168)
Malfunction detection
System stops due to malfunction.
Backup operation starts.
Operates without faulty constant
speed (STD) compressor. (Note 1)
Returns to normal operation.
No malfunction
3 hours elapse.
Remote controller reset
Malfunction
occurs again.
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...