Si33-105
Test Operation
Test Operation R407C PLUS Series Heat Recovery System
125
1.11.2
Emergency Operation
:
Set in setting mode 2. Operates the system when an outdoor unit malfunctions.
1. When an inverter type outdoor unit malfunctions
When an inverter type compressor malfunctions, you can continue operation using constant
speed type compressors only.
Emergency Operation Method
1. Set to “EMG” in setting mode 2.
and
2. All indoor units connected to this outdoor unit are turned on by thermostat.
Emergency operation stops at the following conditions.
1. Emergency operation mode is reset on outdoor unit PC board.
or
2. One or more indoor units connected to this outdoor unit are turned off by thermostat.
Setting of Emergency Mode
Setting Method
LED Display
H1P H2P H3P H4P H5P H6P H7P
Hold down the Mode button for 5 seconds to change to
setting Mode 2.
8
7
7
7
7
7
7
Push SET button and select LED display to “Emergency
Mode”.
8
7
7
7
7
7
7
Push the RETURN button.
8
7
7
7
7
7
9
Push SET button and select LED display as shown right.
8
7
7
7
7
9
7
Push the RETURN button to enter “Emergency Mode”.
All indoor units must be thermostat ON.
8
7
7
7
7
8
7
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...