Si33-105
Outline of Control (Outdoor Unit) < Symbols using in this manual >
Function R407C PLUS Series Heat Recovery System
51
3.1.2
Malfunction Stop by Pe
!
Unit is conducted malfunction stop (manual reset) when Pe becomes low to prevent
compressor from seizing.
Contents
!
Malfunction judgement conditions
Condition
Condition
3.1.3
Malfunction Stop by Td
!
Unit is conducted malfunction stop (manual reset) when Td becomes high to prevent
compressor from seizing.
Contents
!
Malfunction judgement conditions
•
In compressor operation
•
Pe<0 MPa (–37.0˚C)
•
Not in defrosting and oil return operation
•
Elapsed time of 10 minutes or more after
defrosting and oil return operation completion
•
Pe
≥
0.06 MPa(–26.7˚C)
→
•
Stops operation when low
pressure error (E4) is detected.
→
•
Resets malfunction.
I
&
H
(V2554)
•
In compressor operation
•
Th7–Te>45˚C and Pe<0.15 MPa (–16.5˚C)
continues for 3 minutes
•
Injection on inverter side = ON
•
After turning on power supply, within 20 minutes
after the initial startup of compressor
•
Compressor stop
→
•
Stops operation when low
pressure error (E4) is detected.
→
•
Resets malfunction.
I
&
H
(V2555)
•
HTdi
≥
130˚C
•
HTds1
≥
130˚C
•
HTds2
≥
130˚C
•
HTdi<115˚C
•
HTs1<115˚C
•
HTs2<115˚C
•
In compressor operation
•
OR
→
•
Stops operation when discharge
pipe temperature error (F3) is
→
•
Resets malfunction.
I
&
H
(V2556)
Summary of Contents for R407C PLUS
Page 1: ...System R407C PLUS Series Heat Recovery System Si33 105 Service Manual ...
Page 11: ...Introduction Si33 105 x ...
Page 41: ...Specifications Si33 105 30 Specifications R407C PLUS Series Heat Recovery System ...
Page 147: ...Test Operation Si33 105 136 Test Operation R407C PLUS Series Heat Recovery System ...
Page 263: ...Si33 105 iv Index ...