SiENBE04-512A
Control Specification
Function and Control
63
3.15 Facility Setting Jumper (cooling at low outdoor
temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment (such as
computer)). Never use it in a residence or office (the space where there is a human).
Detail
You can expand the operation range to –15°C by cutting jumper 8 (J8) on the PCB. If the
outdoor temperature falls to –20°C or lower, the operation will stop. If the outdoor temperature
rises, the operation will start again.
Caution
1. If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4. Cutting jumper 8 (J8) sets the indoor fan tap to the highest position. Notify the user about
this.
PCB
C
u
t J
8
with nipper
s
or
a
s
imil
a
r tool
s
.
S
90
S8
0
S
70
J1
J
3
J4
J5
J6
J7
J
8
SiENBE04-512A.book Page 63 Friday, October 5, 2007 1:49 PM
Summary of Contents for FTKS20CVMB(9)
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions...
Page 37: ...Specifications SiENBE04 512A 28 Specifications...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure...
Page 229: ...Others SiENBE04 512A 220 Others...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix...