Troubleshooting
SiENBE04-512A
112
Service Diagnosis
4.11 Four Way Valve Abnormality
Remote Control
Display
EA
Method of
Malfunction
Detection
The indoor air temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if
they function within their normal ranges in the operating mode.
Malfunction
Decision
Conditions
A following condition continues over 10 minute after operating 5 minutes.
Cooling / dry operation
(room temp. – indoor heat exchanger temp.) < –5°C
Heating
(indoor unit heat exchanger temp. – room temp.) < –5°C
Supposed
Causes
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Four way valve coil or harness defective
Four way valve defective
Foreign substance mixed in refrigerant
Insufficient gas
SiENBE04-512A.book Page 112 Friday, October 5, 2007 1:49 PM
Summary of Contents for FTKS20CVMB(9)
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions...
Page 37: ...Specifications SiENBE04 512A 28 Specifications...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure...
Page 229: ...Others SiENBE04 512A 220 Others...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix...