SiENBE04-512A
Troubleshooting
Service Diagnosis
103
4.3
Freeze-up Protection Control or High Pressure Control
Remote Control
Display
A5
Method of
Malfunction
Detection
High pressure control (heat pump model only)
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
Freeze-up protection control (operation halt) is activated during cooling operation according
to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
SiENBE04-512A.book Page 103 Friday, October 5, 2007 1:49 PM
Summary of Contents for FTKS20CVMB(9)
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions...
Page 37: ...Specifications SiENBE04 512A 28 Specifications...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure...
Page 229: ...Others SiENBE04 512A 220 Others...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix...