Outdoor Unit / ARK(X)S-C
SiENBE04-512A
176
Removal Procedure
3
Remove the sheets of
putty.
Cut the pipe with a tube
cutter.
4
Heat up the brazed part
and withdraw the piping
with pliers.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to break
the pipes by pressing it
excessively by pliers when
withdrawing it.
Step
Procedure
Points
T
ub
e c
u
tter
(R
3
2
8
0)