Service Check Function
SiENBE04-512A
98
Service Diagnosis
3. Service Check Function
In the ARC433A series remote control, the temperature display sections on the main unit
indicate corresponding codes.
Check Method 1
1. When the timer cancel button is held down for 5 seconds, a “00” indication flashes on the
temperature display section.
2. Press the timer cancel button repeatedly until a continuous beep is produced.
The code indication changes in the sequence shown below, and notifies with a long beep.
Note:
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the timer cancel button down for 5 seconds. The code
display also cancels itself if the button is not pressed for 1 minute.
No.
Code
No.
Code
No.
Code
1
OO
12
C7
23
HO
2
U4
13
H8
24
E1
3
F3
14
J3
25
P4
4
E6
15
A3
26
L3
5
L5
16
A1
27
L4
6
A6
17
C4
28
H6
7
E5
18
C5
29
H7
8
F6
19
H9
30
U2
9
C9
20
J6
31
UH
10
UO
21
UA
32
EA
11
E7
22
A5
33
AH
(R
3
0
38
)
<
ARC4
33
A1, A2
>
TIMER CANCEL button
It c
a
ncel
s
the timer
s
etting.
SiENBE04-512A.book Page 98 Friday, October 5, 2007 1:49 PM
Summary of Contents for FTKS20CVMB(9)
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions...
Page 37: ...Specifications SiENBE04 512A 28 Specifications...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure...
Page 229: ...Others SiENBE04 512A 220 Others...