ESIE05-04
Field Settings
Part 4 – Commissioning and Test Run
4–17
3
4
5
1
Note: Monitoring mode
Air flow direction
setting
Set the air flow direction of the indoor units as given in the table below. This setting is needed when
the optional air outlet blocking pad has been installed. The “Second code No” is factory set to “01”.
OFF
OFF
ON
ON
INDOOR
FAN
LL speed or set speed
THERMO
1 min
1 min
6 min
6 min
Mode No
First code No
Second code No
Setting
13 or 23
1
01
F: four-direction air flow
02
T: three-direction air flow
03
W: two direction air flow