ESIE05-04
Field Settings
Part 4 – Commissioning and Test Run
4–13
3
4
5
1
2.4
Overview of the Field Settings on the Indoor Units
Field settings
The table below contains the possible field settings of all indoor units.
Mode
No.
First
code No.
Description of the setting
Second code No.
01
02
03
04
10 or 20
0
Filter counter
Light
contamination
heavy
contamination
—
—
1
Filter type
Long
Super long
External
Oil mist
2
Remote thermistor of the
remote controller
TH1 = rem.
controller
TH1 = air
return
—
—
3
Filter display
Filter indic.
No filter indic.
—
—
11 or 21
0
Number indoor to 1 outdoor
Pair
Twin
Triple
Double twin
1
Unified or indiv. set twin
Group setting
Indiv. setting
—
—
2
Fan OFF at thermostat OFF
LL-speed
OFF
—
—
12 or 22
0
KRP1B51/52/53 X1/X2 output
Thermostat
ON
Option
Operation
Malfunction
1
EKRORO
Forced OFF
ON/OFF oper-
ation
—
—
3
Fan speed heating thermostat
OFF
LL-speed
Set speed
Continuously
OFF
—
5
Automatic restart
Disabled
Enabled
—
—
13 or 23
0
Ceiling height setting
Normal
High
Extra high
—
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
1
Selection of air flow direction
(setting for when a blocking
pad kit has been inst alled).
4-way flow
3-way flow
2-way flow
—
3
Horizontal discharge grill
Enabled
Disabled
—
—
4
Air flow direction adjust range
setting
Draft preven-
tion
Standard
Ceil soil pre-
vention
—
5
Field fan speed changeover air
outlet (domestic only)
Standard
Option 1
Option 2
—
6
External static pressure
Normal
High
Low
—
14 or 24
0
Additional timer to guard timer
0 s
5 s
10 s
15 s
1b
(Only in
case of
BRC1D52)
0
Permission level setting
Level 2
Level 3
—
—
1
Leave home function
Not
permitted
Permitted
—
—
2
Thermostat sensor in remote
controller (for limit operation
and leave home function only)
Use
Not use
—
—
Summary of Contents for FHQ100BUV3B
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...