ESIE05-04
Functional concept
Part 2 – Functional Description
2–23
3
2
4
5
1
1.18
Indoor Unit Fan Control
Outline
During compressor start and stop control, the indoor fan will receive instruction from the outdoor unit
in order to protect the compressor from receiving liquid and to assure a smooth compressor start up:
Q
Indoor fan control before compressor stop
Q
Indoor fan control during compressor stop
Q
Indoor fan control before compressor startup
Q
Indoor fan control at compressor startup
Before compressor
stop
After thermostat off or remote-controller signal off has been sent from the outdoor unit to the indoor
unit, the compressor will keep on running for a period of time in order to execute the "residual pump
down operation". During this pump down operation, the indoor fan will keep on operating.
Purpose:
Q
Cooling: Minimize the remaining refrigerant amount in indoor unit heat exchanger
Q
Heating: Lower the high pressure by avoiding high temperature build up around the indoor unit heat
exchanger.
During compressor
stop
Before compressor
startup
Indoor fan tap
Indoor cooling / Automatic
cooling
Thermostat OFF
L
Remote controller OFF
LL
Indoor heating / Automatic
heating
Thermostat OFF
LL
Remote controller OFF
LL
Indoor drying
Thermostat OFF
LL
Remote conntrolle OFF
LL
Indoor fan tap
Indoor cooling / Automatic
cooling
Thermostat OFF
Remote controller setting
Remote controller OFF
OFF
Indoor heating / Automatic
heating
Thermostat OFF
LL
Remote controller OFF
OFF
Indoor drying
Thermostat OFF
OFF
Remote controller OFF
OFF
Indoor fan tap
Indoor cooling / Automatic cooling
Remote controller setting
Indoor heating / Automatic heating
OFF
Indoor drying
L
Summary of Contents for FHQ100BUV3B
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...