Error Codes
ESIE05-04
3–40
Part 3 – Troubleshooting
3
1
3
4
5
2.7
Thermistor Abnormality (
C4, C5, C9
)
Error code
The table below describes the two thermistor abnormalities.
LED indications
The table below shows the LED indications.
Error generation
The error is generated when during compressor operation:
Q
Thermistor input > 4.96 V, or
Q
Thermistor output < 0.04 V.
Causes
The possible causes are:
Q
Malfunctioning connector connection
Q
Malfunctioning thermistor
Q
Malfunctioning PCB
Q
Broken or disconnected wire.
Checking
thermistors
See page 3–56.
Error
Description
C4
Malfunctioning heat exchanger thermistor system.
C5
Malfuncioning gaspipe thermistor system.
C9
Malfunctioning suction air thermistor system.
Operation
HAP (green)
HBP (green)
Normal
c
c
Malfunctioning
c
c
Summary of Contents for FHQ100BUV3B
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...