Functional concept
ESIE05-04
2–18
Part 2 – Functional Description
3
1
2
4
5
Float switch
activation during
thermostat ON
1
The thermostat is immediately turned OFF.
2
The drain pump continues to operate for minimum 10 minutes (even if abnormality is solved within
the 10 minutes).
3
If the float switch closes again within 80 seconds, cooling operation can restart within the 10
minutes recovery period.
Used inputs
Float switch
Water level
abnormality
ON
OFF
Abnormal
Normal
5 min
5 min
5 s
ON
OFF
Normal
Compressor
Drain pump
Error processing
Input
Connection on indoor PCB
Connection on outdoor PCB
Float switch (33H)
X15A
—
Summary of Contents for FHQ100BUV3B
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...