1.9
Forced Thermostat OFF
Outline
The unit will perform the forced thermostat off function in following conditions:
Condition 1
(cooling)
Thermostat off due to freeze-up prevention.
Prevent the indoor unit heat exchanger from freezing in cooling operation when one of the below
conditions is applicable:
Q
Indoor unit heat exchanger temperature < -5°C for 1 minute continuously.
Q
Indoor unit heat exchanger temperature < -1°C for 40 minutes accumulated.
Condition 2
(heating)
Thermostat off due to high outdoor temperature.
When the outside temperature is > 30°CDB in heating mode, the unit will conduct a forced thermostat
off operation to protect the system.
Reference
"Freeze Prevention Function". Refer to page 2-14.
Summary of Contents for FHQ100BUV3B
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...