Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Preferential kWh rate
A.6.2.1
[D-00]
R/W
0: None
2: BUH only
A.6.2.2
[D-05]
R/W
0: Forced off
1: As normal
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2
[4-09]
R/W
0: Current
1: Power
A.6.3.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
A.6.3.4
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1
[5-05]
Amp. limits for DI
Limit DI1
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.2
[5-06]
Amp. limits for DI
Limit DI2
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.3
[5-07]
Amp. limits for DI
Limit DI3
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.4
[5-08]
Amp. limits for DI
Limit DI4
R/W
0~50 A, step: 1 A
50 A
A.6.3.6.1
[5-09]
kW limits for DI
Limit DI1
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2
[5-0A]
kW limits for DI
Limit DI2
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3
[5-0B]
kW limits for DI
Limit DI3
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4
[5-0C]
kW limits for DI
Limit DI4
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.7
[4-01]
R/W
0: None
1: BSH
2: BUH
└─
Averaging time
A.6.4
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Ext amb. sensor offset
A.6.5
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Overview settings
A.8.1
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
R/W
25~55°C, step: 1°C
35°C
A.8.2
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
R/W
25~55°C, step: 1°C
45°C
A.8.3
[0-02]
High ambient temp. for LWT add zone heating WD curve.
R/W
10~20°C, step: 1°C
15°C
A.8.4
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
R/W
-20~5°C, step: 1°C
-10°C
A.8.5
[0-04]
R/W
8
A.8.6
[0-05]
R/W
12
A.8.7
[0-06]
R/W
35
A.8.8
[0-07]
R/W
20
A.8.9
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
R/W
35~55°C, step: 1°C
55°C
A.8.10
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
R/W
55~70°C, step: 1°C
70°C
A.8.11
[0-0D]
High ambient temp. for DHW WD curve.
R/W
10~20°C, step: 1°C
15°C
A.8.12
[0-0E]
Low ambient temp. for DHW WD curve.
R/W
-20~5°C, step: 1°C
-10°C
A.8.13
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
R/W
-20~5°C, step: 1°C
-10°C
A.8.14
[1-01]
High ambient temp. for LWT main zone heating WD curve.
R/W
10~20°C, step: 1°C
15°C
A.8.15
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
R/W
25~55°C, step: 1°C
35°C
A.8.16
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
R/W
25~55°C, step: 1°C
25°C
A.8.17
[1-04]
R/W
0: Disabled
A.8.18
[1-05]
R/W
0: Disabled
A.8.19
[1-06]
R/W
20
A.8.20
[1-07]
R/W
35
A.8.21
[1-08]
R/W
22
A.8.22
[1-09]
R/W
18
A.8.23
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8.24
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.8.25
[2-01]
R/W
0: No
1: Yes
A.8.26
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.8.27
[2-03]
R/W
60°C
A.8.28
[2-04]
R/W
40~60 min, step: 5 min
60 min
A.8.29
[2-05]
R/W
4~16°C, step: 1°C
12°C
A.8.30
[2-06]
R/W
0: Disabled
1: Enabled
Room antifrost temperature
Room frost protection
What is the averaging time for the outdoor temp?
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature?
How long must the tank temperature be maintained?
--
--
--
--
--
--
kW value
Priority
--
--
--
--
Mode
Type
Amp. value
Allowed heaters
Forced pump OFF
EHVH0*S18CA3VF
4P366223-1 - 2014.02