![background image](http://html1.mh-extra.com/html/daikin/erlq004cav3/erlq004cav3_installers-reference-manual_4059854058.webp)
8
Configuration
Installer reference guide
58
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
Pump operation
The pump operation field setting apply to the pump operation logic
only when [F0D]=1.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [402]. When
the pump operation is enabled, the pump operation is possible at all
outdoor temperatures.
#
Code
Description
N/A
[F00]
Pump operation:
▪ 0: Disabled if outdoor temperature is
higher than [402].
▪ 1:
Possible
at
all
outdoor
temperatures.
Pump operation during flow abnormality [F09] defines whether the
pump stops at flow abnormality or allow to continue operation when
flow abnormality occurs. This functionality is only valid in specific
conditions where it is preferable to keep the pump active when T
a
<4°C (pump will be activated for 10 minutes and deactivated after 10
minutes). Daikin shall NOT be held liable for any damage resulting
this functionality.
#
Code
Description
N/A
[F09]
Pump continue operation when flow
abnormality:
▪ 0: Pump will be deactivated.
▪ 1: Pump will be activated when T
a
<4°C (10 minutes ON – 10 minutes
OFF)