12
Troubleshooting
Installer reference guide
68
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
Possible causes
Corrective action
Too much heat pump capacity is
used for heating domestic hot
water (applies only to
installations with a domestic hot
water tank)
Check and make sure that the
“space heating priority” settings
have been configured
appropriately:
▪ Make sure that the “space
heating priority status” has
been enabled. Go to [A.8] >
Installer settings > Overview
settings [502]
▪ Increase the “space heating
priority
temperature”
to
activate
backup
heater
operation at a higher outdoor
temperature. Go to [A.8] >
Installer settings > Overview
settings [503]
12.2.7
Symptom: The pressure at the tapping
point is temporarily unusual high
Possible causes
Corrective action
Failing or blocked pressure relief
valve.
▪ Flush and clean the complete
tank
including
the
piping
between pressure relief valve
and the cold water inlet.
▪ Replace the pressure relief
valve.
12.2.8
Symptom: Decoration panels are pushed
away due to a swollen tank
Possible causes
Corrective action
Failing or blocked pressure relief
valve.
Contact your local dealer.
12.2.9
Symptom: Tank disinfection function is
NOT completed correctly (AHerror)
Possible causes
Corrective action
The disinfection function was
interrupted by domestic hot water
tapping
Program the startup of the
disinfection function when the
coming 4 hours NO domestic hot
water tapping is expected.
Large domestic hot water tapping
happened recently before the
programmed startup of the
disinfection function
When the Domestic hot water >
Setpoint mode > Reheat or
sched. is selected, it is
recommended to program the
startup the disinfection function
at least 4 hours later than the last
expected large hot water tapping.
This startup can be set by
installer settings (disinfection
function).
When the Domestic hot water >
Setpoint mode > Scheduled only
is selected, it is recommended to
program a Storage eco 3 hours
before the scheduled startup of
the disinfection function to
preheat the tank.
12.2.10
Symptom: The energy metering
(produced heat) is NOT working correctly
Possible causes
Corrective action
The measured temperatures for
produced heat calculation are
NOT accurate.
Execute a calibration of the
system by performing an actuator
test run of the pump (see
"9.5 To
perform an actuator test run" on
page 62
).
12.3
Solving problems based on error
codes
When a problem happens, an error code appears on the user
interface. It is important to understand the problem and to take
countermeasure before resetting the error code. This should be
done by a licensed installer or by your local dealer.
This chapter gives you an overview of all error codes and the
content of the error code as it appears on the user interface.
For a more detailed troubleshooting guideline for each error, please
see the service manual.
12.3.1
Error codes: Overview
Error codes of the outdoor unit
Error code
Detailed error
code
Description
A5
00
OU: High pressure cooling/Peak
cut/ freeze protection problem.
Please contact your dealer.
E1
00
OU: PCB defect.
Power reset required.
Please contact your dealer.
E3
00
OU: Actuation of high pressure
switch (HPS).
Please contact your dealer.
E5
00
OU: Overheat of inverter
compressor motor.
Please contact your dealer.
E6
00
OU: Compressor startup defect.
Please contact your dealer.
E7
00
OU: Malfunction of outdoor
unit fan motor. Please contact
your dealer.
E8
00
OU: Power input overvoltage.
Please contact your dealer.
EA
00
OU: Cool/heat switchover
problem.
Please contact your dealer.
H0
00
OU: Voltage/current sensor
problem.
Please contact your dealer.
H3
00
OU: Malfunction of high
pressure switch (HPS)
Please contact your dealer.
Summary of Contents for ERLQ004CAV3
Page 100: ...2 8 ...
Page 107: ......