Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
A.3.1.1.3
[1-02]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
25~55°C, step: 1°C
35°C
A.3.1.1.3
[1-03]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W
25~55°C, step: 1°C
25°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.6.1
[F-0B]
Shut-off valve
Thermo On/OFF
R/W
0: No
1: Yes
A.3.1.1.7
[9-0B]
R/W
0: Quick
1: Slow
└──────────────────
Additional
A.3.1.2.1
R/W
0: Absolute
1: Weather dep.
2: Abs + scheduled
3: WD + scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~55°C, step: 1°C
55°C
A.3.1.2.3
[0-00]
Set weather-dependent heating
Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W
25~55°C, step: 1°C
35°C
A.3.1.2.3
[0-01]
Set weather-dependent heating
Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W
25~55°C, step: 1°C
45°C
A.3.1.2.3
[0-02]
Set weather-dependent heating
High ambient temp. for LWT add zone heating
WD curve.
R/W
10~20°C, step: 1°C
15°C
A.3.1.2.3
[0-03]
Set weather-dependent heating
Low ambient temp. for LWT add zone heating
WD curve.
R/W
-20~5°C, step: 1°C
-10°C
└──────────────────
Delta T emitter
A.3.1.3.1
[9-09]
Delta T emitter
Heating
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.3
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 0,5 °C
1: 1 °C
└─
Operation range
A.3.3.1
[4-02]
R/W
14~25°C, step: 1°C
25°C
└─
Domestic hot water (DHW)
└─
Setpoint mode
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Scheduled DHW
A.4.2.1
R/W
0: Presets
1: Custom
A.4.2.2
R/W
0: Absolute
1: Weather dep.
A.4.2.3
[0-0B]
Weather-dependent curve
Leaving water value for high ambient temp. for
DHW WD curve.
R/W
35~55°C, step: 1°C
55°C
A.4.2.3
[0-0C]
Weather-dependent curve
Leaving water value for low ambient temp. for
DHW WD curve.
R/W
55~70°C, step: 1°C
70°C
A.4.2.3
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~20°C, step: 1°C
15°C
A.4.2.3
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-20~5°C, step: 1°C
-10°C
└─
Setpoint readout
A.4.3.1
R/W
0: Temperature
1: Graphical
A.4.3.2.1
Conversion persons
1 person
R/W
30~80°C, step: 1°C
42°C
A.4.3.2.2
Conversion persons
2 persons
R/W
0~20°C, step: 1°C
6°C
A.4.3.2.3
Conversion persons
3 persons
R/W
0~20°C, step: 1°C
15°C
A.4.3.2.4
Conversion persons
4 persons
R/W
0~20°C, step: 1°C
17°C
A.4.3.2.5
Conversion persons
5 persons
R/W
0~20°C, step: 1°C
1°C
A.4.3.2.6
Conversion persons
6 persons
R/W
0~20°C, step: 1°C
1°C
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.4.4.4
[2-03]
R/W
60°C
A.4.4.5
[2-04]
R/W
40~60 min, step: 5 min
60 min
└─
Maximum setpoint
A.4.5
[6-0E]
60°C
└─
Heat sources
└─
Backup heater
A.5.1.1
[4-00]
R/W
0: Limit
1: Enable
2: Only DHW
A.5.1.2
[4-06]
R/W
0: No
1: Yes
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
└─
System operation
LWT setpoint mode
Emitter type
Modulated LWT
Setpoint readout type
Storage comfort SP mode
Schedule temperatures
Space heating OFF temp
Room temp. offset
Ext. room sensor offset
Room temp. step
Auto emergency operation
Equilibrium temp.
Disinfection
Operation day
Start time
Temperature target
Duration
Operation mode
4P366223-1 - 2014.02