7/8
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
A.8.95
[8-07]
R/W
18
A.8.96
[8-08]
R/W
20
A.8.97
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
A.8.98
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
A.8.99
[9-00]
R/W
37~55°C, step: 1°C
55°C
A.8.100
[9-01]
R/W
15~37°C, step: 1°C
25°C
A.8.101
[9-02]
R/W
22
A.8.102
[9-03]
R/W
5
A.8.103
[9-04]
R/W
1~4°C, step: 1°C
1°C
A.8.104
[9-05]
R/W
15~37°C, step: 1°C
25°C
A.8.105
[9-06]
R/W
37~55°C, step: 1°C
55°C
A.8.106
[9-07]
R/W
5
A.8.107
[9-08]
R/W
22
A.8.108
[9-09]
R/W
3~10°C, step: 1°C
5°C
A.8.109
[9-0A]
R/W
5
A.8.110
[9-0B]
R/W
0: Quick
1: Slow
A.8.111
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
A.8.112
[A-00]
0
A.8.113
[A-01]
0
A.8.114
[A-02]
1
A.8.115
[A-03]
0
A.8.116
[A-04]
0
A.8.117
[B-00]
0
A.8.118
[B-01]
0
A.8.119
[B-02]
0
A.8.120
[B-03]
0
A.8.121
[B-04]
0
A.8.122
[C-00]
R/W
0
A.8.123
[C-01]
1
A.8.124
[C-02]
R/W
0: No
1: Bivalent
2: -
3: -
A.8.125
[C-03]
R/W
-25~25°C, step: 1°C
0°C
A.8.126
[C-04]
R/W
2~10°C, step: 1°C
3°C
A.8.127
[C-05]
R/W
0: -
1: Thermo ON/OFF
2: C/H request
A.8.128
[C-06]
R/W
0: -
1: Thermo ON/OFF
2: C/H request
A.8.129
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
A.8.130
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
A.8.131
[C-09]
R/W
0: Normally open
1: Normally closed
A.8.132
[D-00]
R/W
0: None
1: --
2: BUH only
3: --
A.8.133
[D-01]
R/W
0: No
1: Active open
2: Active closed
A.8.134
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. shunt
A.8.135
[D-03]
R/W
0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C)
2: Enabled, shift 4°C (from -2 to 2°C)
3: Enabled, shift 2°C (from -4 to 4°C)
4: Enabled, shift 4°C (from -4 to 4°C)
A.8.136
[D-04]
R/W
0: No
1: Yes
A.8.137
[D-05]
R/W
1
A.8.138
[D-07]
R/W
0: No
A.8.139
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.8.140
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
A.8.141
[E-00]
R/O
0: LT split
A.8.142
[E-01]
R/O
0:08
A.8.143
[E-02]
R/O
1: Type 2
A.8.144
[E-03]
R/O
1: 1 step
A.8.145
[E-04]
R/O
1: Yes
A.8.146
[E-05]
R/W
1: Yes
A.8.147
[E-06]
R/O
1: Yes
A.8.148
[E-07]
R/W
1: Backup heater
A.8.149
[E-08]
R/W
0: Disabled
1: Enabled
A.8.150
[E-09]
0
A.8.151
[F-00]
R/W
0: Disabled
1: Enabled
Pump operation allowed outside range.
Is the power saving function available on the outdoor unit?
Is a DHW tank installed in the system?
Is the domestic hot water tank installed?
Which type of electrical heater for DHW is installed?
Power saving function for outdoor unit.
--
Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement?
Which type of unit is installed?
Which type of compressor is installed?
What is the indoor unit software type?
What is the number of backup heater steps?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
--
Is a solar kit connected?
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
Which heaters are permitted if prefer. kWh rate PS is cut?
--
Domestic heating water priority.
--
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
--
--
--
--
--
--
--
What emitter type is connected to the main LWT zone?
Room temperature hysteresis.
--
--
--
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
--
--
What is the desired delta T in heating?
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
--
--
--
--
EHVH0*S18CA3VF