![background image](http://html1.mh-extra.com/html/daikin/erlq004cav3/erlq004cav3_installers-reference-manual_4059854090.webp)
15 Technical data
Installer reference guide
90
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
15.5
Technical specifications
15.5.1
Technical specifications: Outdoor unit
Nominal capacity and nominal input
Outdoor units
ERLQ004CAV3
ERLQ006CAV3
ERLQ008CAV3
Indoor units
EHVH04S18CA3VF
EHVH08S18CA3VF
Condition 1
(a)
Heating capacity
Minimum
1.80 kW
Nominal
4.40 kW
6.00 kW
7.40 kW
Maximum
5.12 kW
8.35 kW
10.02 kW
Heating PI
Nominal
0.87 kW
1.27 kW
1.66 kW
COP
Nominal
5.04
4.74
4.45
EER
Nominal
—
Condition 2
(a)
Heating capacity
Minimum
1.80 kW
Nominal
4.03 kW
5.67 kW
6.89 kW
Maximum
4.90 kW
7.95 kW
9.53 kW
Heating PI
Nominal
1.13 kW
1.59 kW
2.01 kW
COP
Nominal
3.58
3.56
3.42
EER
Nominal
—
(a)
Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (DT=5°C).
(b)
Ambient temperature DB/WB 7°C/6°C – leaving water condenser 45°C (DT=5°C).
Technical specifications
Outdoor units
ERLQ004CAV3
ERLQ006CAV3
ERLQ008CAV3
Indoor units
EHVH04S18CA3VF
EHVH08S18CA3VF
Casing
Colour
Ivory white
Material
Polyester painted galvanised steel
Dimensions
Packing (H×W×D)
797×990×390 mm
Unit (H×W×D)
735×832×307 mm
Weight
Machine weight
54 kg
56 kg
Gross weight
57 kg
59 kg
Packing
Material
EPS, carton
Weight
3 kg
Heat exchanger
Specifications
Length
845 mm
Nr. of rows
2
Fin pitch
1.8 mm
Nr. of passes
—
Face area
—
Nr. of stages
32
Tube type
HiXa(8)
Fin
Type
WF fin
Treatment
Anticorrosion treatment (PE)
Fan
Type
Propeller
Quantity
1
Air flow rate (nominal at
230 V)
Heating
—
Discharge direction
Horizontal
Motor
Quantity
1
Output
53