5 Application guidelines
Installer reference guide
15
ERLQ004~008CA + 08S18CA3VF
Daikin Altherma low temperature split
4P3662261 – 2014.01
Setup
▪ Integrate the auxiliary boiler as follows:
a
b c d e
f
f
g
h
j
FHL1
FHL2
FHL3
M
h
i
i
l
k
m
n
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Shutoff valve
g
Motorised 3way valve (delivered with DHW tank)
h
Nonreturn valve (field supply)
i
Shutoff valve (field supply)
j
Collector (field supply)
k
Auxiliary boiler (field supply)
l
Aquastat valve (field supply)
m
DHW tank
n
Heat exchanger coil
FHL1...3
Under floor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
▪ Make sure the return water to the heat pump does NOT exceed
55°C. To do so:
▪ Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
▪ Install an aquastat valve in the return water flow of the
heat pump.
▪ Set the aquastat valve to close above 55°C and to open below
55°C.
▪ Install nonreturn valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already premounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HB).
▪ Connect X1 and X2 (changeover to external heat source) on the
PCB to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see
"5.2 Setting up the space heating
system" on page 10
.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between
indoor unit and auxiliary boiler.
▪ Because the outdoor temperature is measured by the
outdoor unit air thermistor, install the outdoor unit in the
shadow so that it is NOT influenced or turned ON/OFF
by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary
contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see
"5.2 Setting up the space
heating system" on page 10
).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ …
▪ Setup: Connect the following field wiring:
L
N
H
Com
A
K2A
K1A
X2M
BTI
K2A
K1A
Indoor/Auto/Boiler
1 2 3 4
X Y
Indoor
B
TI
Boiler thermostat input
A
Auxiliary contact (normal closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of indoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Indoor
Indoor unit
Auto
Automatic
Boiler
Boiler
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between
indoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that
it is NOT influenced or turned ON/OFF by direct
sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.