7
|
Unit installation
Installer reference guide
78
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
7.2.3 To close the outdoor unit
1
Close the switch box cover.
2
Close the service cover.
NOTICE
When closing the outdoor unit cover, make sure that the tightening torque does NOT
exceed 4.1 N•m.
7.2.4 To open the indoor unit
NOTICE
The top cover can only be removed if the switch box is lowered.
Overview
a
b
a
User interface panel
b
Switch box cover
Open
1
Remove the user interface panel. Open the hinges at the top and slide the
interface panel downwards.
1
2
2
Remove the switch box cover.
NOTICE
Do NOT damage or remove the foam sealing of the switch box.
3
Disconnect the ground connection from the top cover of the switch box.