Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[2-05]
R/W
4~16°C, step: 1°C
12°C
9.I
[2-06]
R/W
0: No
1: Yes
9.I
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0E]
R/W
20~50 A, step: 1 A
50 A
9.I
[3-00]
R/W
0: manual
1: automatic
9.I
[3-01]
R/W
0
9.I
[3-02]
R/W
1
9.I
[3-03]
R/W
4
9.I
[3-04]
R/W
2
9.I
[3-05]
R/W
1
9.I
[3-06]
R/W
18~30°C, step: 1°C
30°C
9.I
[3-07]
R/W
12~18°C, step: 1°C
12°C
9.I
[3-08]
R/W
25~35°C, step: 1°C
35°C
9.I
[3-09]
R/W
15~25°C, step: 0,5 1°C
15°C
9.I
[3-0A]
What is the pump model
R/O
0: pump model 0
1: pump model 1
9.I
[4-00]
R/W
0: Restricted
1: Allowed
2: Only DHW
9.I
[4-01]
R/W
0: None
1: Booster Heater
2: Backup Heater
9.I
[4-02]
R/W
14~35°C, step: 1°C
22°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.I
[4-07]
3
9.I
[4-08]
R/W
0: No
1: Continuous
2: Inputs
3: Current Sensor
9.I
[4-09]
R/W
0: Amp
1: kW
9.I
[4-0A]
R/W (*5,
*6, *7)
R/O (*4)
0: 1 (*4, *7)
1: 1/1+2 (*5, *6)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No
1: Yes
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
What emitter type is connected to the main LWT zone?
What emitter type is connected to the additional LWT zone?
What is the maximum allowed current over the heatpump ?
Is auto restart of the unit allowed?
--
--
--
--
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
--
What is the minimum desired room temperature in cooling?
What is the BUH operation mode?
Which electric heater has priority?
Below which outdoor temperature is heating allowed?
Operation permission of the booster heater.
Water pipe freeze prevention
--
Emergency
--
Which power limitation mode is required on the system?
Which power limitation type is required?
Backup heater configuration
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
What is the equilibrium temperature for the building?
Space heating priority.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
Space heating priority temperature.
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
What is the requested limit for DI2?
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) *EKECBUA3V*_(*7) *EKECBUA6V*_(*8) *EKECBUA9W*_(*9) BUH less_
(*10) 04P_(*11) 08P