Unit installation
Installer reference guide
75
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
INFORMATION
▪
For HPSU models, the value of "Installation height (H)" is considered 600 mm to
comply to IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪
For intermediate A
room
values (i.e. when A
room
is between two values from the
table), consider the value that corresponds to the lower A
room
value from the
table. If A
room
=12.5 m
2
, consider the value that corresponds to "A
room
=12 m
2
".
Table 2: Minimum floor area: indoor unit
m
c
(kg)
Minimum floor area (m²)
H=600 mm
1.84
28.81
1.86
29.44
1.88
30.08
1.90
30.72
INFORMATION
▪
For HPSU models, the value of "Installation height (H)" is considered 600 mm to
comply to IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪
For intermediate m
c
values (i.e. when m
c
is between two values from the table),
consider the value that corresponds to the higher m
c
value from the table. If
m
c
=1.87 kg, consider the value that corresponds to "m
c
=1.88 kg".
▪
Systems with a total refrigerant charge (m
c
) <1.84 kg (i.e. if the piping length is
<27 m) are NOT subjected to any requirements to the installation room.
▪
Charges >1.9 kg are NOT allowed in the unit.
Table 3: Minimum venting opening area for natural ventilation
m
c
m
max
dm=m
c
–m
max
(kg)
Minimum bottom opening area (cm
2
)
H=600 mm
1.9
0.1
1.80
729
1.9
0.3
1.60
648
1.9
0.5
1.40
567
1.9
0.7
1.20
486
1.9
0.9
1.00
418
1.9
1.1
0.80
370
1.9
1.3
0.60
301
1.9
1.5
0.40
216
1.9
1.7
0.20
115
INFORMATION
▪
For floorstanding models, the value of "Installation height (H)" is considered
600 mm to comply to IEC 60335-2-40:2013 A1 2016 Clause GG2.
▪
For intermediate dm values (i.e. when dm is between two dm values from the
table), consider the value that corresponds to the higher dm value from the table.
If dm=1.55 kg, consider the value that corresponds to "dm=1.6 kg".