11
|
Configuration
Installer reference guide
232
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
Tank free energy hysteresis
#
Code
Description
[9.O.2]
[7‑0E]
Range: 2°C~22°C (step: 0.5°C)
The tank free energy hysteresis defines the storage tank limit temperature, above
which heat pump and boiler is stopped in case solar energy is provided and solar
priority is active ([C‑00]=0).
t
[7-0E]
[7-0D]
3°C
[6-00]
T
Sol
T
set
T
HP on
Sol
Free
HP
tank
HP
tank
HP
SH
HP
SH
Tank
SH
T
tank
Preheat
Support
HP
Heat pump
Sol
Solar energy input
HP
tank
Tank heating by heat pump operation
HP
SH
Space heating by heat pump operation
T
tank
Storage tank temperature
Tank
SH
Space heating by tank heating support
T
set
In this example: Tank setpoint (may differ depending on space heating setpoint)
T
Sol
HP (and boiler) off temperature (T
set
+3+[7‑0E])
T
HP on
HP tank heating ON temperature (Tank setpoint–[6‑00])
Free
Tank state:
Free energy
Support
Tank state:
Support
Preheat
Tank state:
Pre heating
NOTICE
If both solar energy and indirect auxiliary boiler is available, make sure that [7-0E] >
[7-0D].
Tank capacity limitation
#
Code
Description
[9.O.3]
[F-0E]
Limiting the capacity used for tank heating
support will prevent the heating support function
taking too much energy from the tank in a short
time.
Range: 0 kW~63 kW (step: 1 kW)
The capacity should be limited to the capacity provided by the heat pump.