11
|
Configuration
Installer reference guide
202
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
Example: setpoint (T
U
)≤maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in storage tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
WD curve
When weather-dependent operation is active the desired tank temperature is
determined automatically depending on the averaged outdoor temperature: low
outdoor temperatures will result in higher desired tank temperatures as the cold
water tap is colder and vice versa.
Also see
"11.4 Weather-dependent curve"
WD curve type
There are 2 methods to define the weather-dependent curves:
▪
2-points
164])
▪
Slope-Offset
In [2.E]
WD curve type
, you can choose which method you want to use.
In [5.E]
WD curve type
, the chosen method is shown read-only (same value as in
[2.E]).
#
Code
Description
[2.E] / [5.E]
N/A
▪
0:
2-points
▪
1:
Slope-Offset
11.5.7 User settings
Overview
The following items are listed in the submenu: