Outdoor Unit / RK(X)H-C, ARK(X)H-C, R(Y)N-C
SiENBE04-512A
210
Removal Procedure
3
Remove the terminal
cover gasket.
Take a note.
U : Red
V : Yellow
W: Blue
2. Remove the compressor.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (In case the refrigerant
gas is exposed to fire, it will
cause toxic gas.)
Apply welding-work sheet or
iron plate so that the flame
of gas welding machine
should not affect the nearby
parts.
Be careful not to burn the
compressor terminal and the
nameplate.
Be careful not to burn the
heat exchanger fin.
Warning
The refrigerator oil of the
compressor may catch fire.
Provide wet cloth for prompt
extinction in emergency.
Caution
From the point of view of
environmental protection, do
not release the refrigerant
gas to the atmosphere, but
always collect it with use of a
collecting device.
1
Remove the nut of the
compressor.
Before starting the work,
make sure that the
refrigerant gas has been
completely removed out of
the refrigerant circulating
system.
2
Heat the soldered
portion of the discharge
side, and disconnect
the discharge pipe.
Step
Procedure
Points
G
as
ket
(R4507)
W
V
U
SiENBE04-512A.book Page 210 Friday, October 5, 2007 1:49 PM
Summary of Contents for ARKH20CVMB7
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Page 37: ...Specifications SiENBE04 512A 28 Specifications ...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Page 229: ...Others SiENBE04 512A 220 Others ...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...