SiENBE04-512A
Outdoor Unit / RK(X)H-C, ARK(X)H-C, R(Y)N-C
Removal Procedure
187
3
Peel off the adhesive
tape at 2 positions of
the insulation sheet.
For prolonged durability, use
filament-reinforced adhesive
tape. (PVC tape can not be
used.)
4
Remove the insulation
sheet.
Step
Procedure
Points
In
su
l
a
tion
s
heet
Adhe
s
ive t
a
pe
(R44
38
)
SiENBE04-512A.book Page 187 Friday, October 5, 2007 1:49 PM