SiENBE04-512A
Others
Others
219
1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two infrared remote controls can be set for
different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the front panel.
(2) Remove the sensor parts cover (2-screws), then remove the electric parts box (1-screw).
(3) Slide the metallic cover to remove it. (4-claws on the electric parts box)
(4) Cut the jumper JA on PCB.
Infrared remote control
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
(R2
8
71)
(R4562)
PCB
JA
JB
JC
1
2
EXI
S
T
CUT
ADDRE
SS
S
en
s
or
p
a
rt
s
cover
Electric
p
a
rt
s
b
ox
Cl
a
w
s
(4 point)
Met
a
llic cover
J4
ADDRE
SS
: JA
J4
EXI
S
T
1
Addre
ss
2
CUT
Jumper
(On indoor control PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto-restart
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
Fan speed setting ;
remote control
setting
Fan rpm is set to “0”
<Fan stop>
SiENBE04-512A.book Page 219 Friday, October 5, 2007 1:49 PM
Summary of Contents for ARKH20CVMB7
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Page 37: ...Specifications SiENBE04 512A 28 Specifications ...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Page 229: ...Others SiENBE04 512A 220 Others ...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...