Others
SiENBE04-512A
218
Others
1. Others
1.1
Test Run from the Remote Control
For Heat pump
In cooling mode, select the lowest programmable temperature; in heating mode, select the
highest programmable temperature.
Trial operation may be disabled in either mode depending on the room temperature.
After trial operation is complete, set the temperature to a normal level.
(26°C to 28°C in cooling mode, 20°C to 24°C in heating mode)
For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling Only
Select the lowest programmable temperature.
Trial operation in cooling mode may be disabled depending on the room temperature.
Use the remote control for trial operation as described below.
After trial operation is complete, set the temperature to a normal level (26°C to 28°C).
For protection, the machine disables restart operation for 3 minutes after it is turned off.
Trial Operation and Testing
1. Measure the supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating mode.
3. Carry out the test operation in accordance with the Operation Manual to ensure that all
functions and parts, such as louver movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is
not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore
the original operation mode when the circuit breaker is opened again.
Trial operation from Remote Control
(1) Press ON/OFF button to turn on the system.
(2) Simultaneously press center of TEMP button and MODE buttons.
(3) Press MODE button twice.
(“
T
” will appear on the display to indicate that Trial Operation mode is selected.)
(4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a
trial operation, press ON/OFF button.
TEMP
ON/OFF
POWERFUL
HOME LEAVE
MODE
FAN
(2)
(1) (4)
(3)
(3)
(R2870)
SiENBE04-512A.book Page 218 Friday, October 5, 2007 1:49 PM
Summary of Contents for ARKH20CVMB7
Page 1: ...SiENBE04 512A Service Manual Inverter Pair Wall Mounted Type C Series D Series ...
Page 17: ...List of Functions SiENBE04 512A 8 List of Functions ...
Page 37: ...Specifications SiENBE04 512A 28 Specifications ...
Page 73: ...Control Specification SiENBE04 512A 64 Function and Control ...
Page 103: ...Instruction SiENBE04 512A 94 System Configuration ...
Page 147: ...Check SiENBE04 512A 138 Service Diagnosis ...
Page 225: ...Outdoor Unit RK X H C ARK X H C R Y N C SiENBE04 512A 216 Removal Procedure ...
Page 229: ...Others SiENBE04 512A 220 Others ...
Page 241: ...Wiring Diagrams SiENBE04 512A 232 Appendix ...