11
|
Configuration
Installer reference guide
160
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
Schedule/Control
Description
[3.2]
Additional zone
>
Heating schedule
Schedule for when the system
is allowed to heat up the
additional zone in heating
mode.
Predefined schedules:
1
Activation screen
: [3.1]
Schedule
Possible actions
:
▪
Off
: When the system is NOT allowed to heat
up the additional zone.
▪
On
: When the system is allowed to heat up the
additional zone.
[3.3]
Additional zone
>
Cooling schedule
Schedule for when the system
is allowed to cool down the
additional zone in cooling
mode.
Predefined schedules:
1
Activation screen
: [3.1]
Schedule
Possible actions
:
▪
Off
: When the system is NOT allowed to cool
down the additional zone.
▪
On
: When the system is allowed to cool down
the additional zone.
[4.2]
Space heating/
cooling
>
Operation mode
schedule
Schedule (per month) for when
to operate the unit in heating
mode and when in cooling
mode.
See
"To set the space operation mode"
193].
[5.5]
Tank
>
Schedule
Schedule for the domestic hot
water tank temperature for
your normal domestic hot
water needs.
Predefined schedules:
1
Activation screen
: Not applicable. This schedule
is automatically activated if the DHW mode is
one of the following:
▪
Schedule only
▪
Sc reheat
Possible actions
:
▪
Comfort
: When to start heating the tank to
the user-defined preset value [5.2]
Comfort
setpoint
.
▪
Eco
: When to start heating the tank to the
user-defined
preset
value
[5.3]
Eco
setpoint
.
▪
Stop
: When to stop heating the tank, even if
the desired tank temperature is not reached
yet.
Note:
In
Sc reheat
mode, the
system also takes the user-defined preset value
[5.4]
Reheat setpoint
into account.