10/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
55°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.I
[6-0E]
R/W
[E-07]=0 or 7 (*3):
40~60°C, step: 1°C
60°C
[E-07]=1 (*4):
40~65°C, step: 1°C
60°C
[E-07]=3 or 8 (*3):
40~75°C, step: 1°C
75°C
[E-07]=5 (*3):
40~80°C, step: 1°C
80°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: Single zone
1: Dual zone
9.I
[7-03]
2.5
9.I
[7-04]
0
9.I
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.I
[7-06]
R/W
0: Disabled
1: Enabled
9.I
[7-07]
R/W
0: Disabled
1: Enabled
9.I
[7-08]
R/O (*3)
R/W (*4)
0: Disabled (*3)
1: Enabled (*4)
9.I
[7-09]
R/W
20
9.I
[7-0A]
R/W
20~95%, step 5%
95%
9.I
[7-0B]
R/W
20~95%, step 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step 5 sec
125 seconds
9.I
[7-0D]
4
9.I
[7-0E]
7
9.I
[8-00]
R/O
0~20 min, step 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
3 hour
9.I
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W
[2-0C]=2:
37~60, step: 1°C
60°C
[2-0C]
≠
2:
37~55, step: 1°C
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-03]
R/W
5~18°C, step: 1°C
7°C
9.I
[9-04]
R/W
1~4°C, step: 1°C
2°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]
≠
2:
37~55, step: 1°C
55°C
9.I
[9-07]
R/W
5~18°C, step: 1°C
7°C
--
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
What is the maximum DHW temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
--
--
Boiler efficiency
Compressor forced off
BBR16 activation
Minimum running time for domestic hot water operation.
Settable lower limit for the PWM of the pump
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the other, in case a
bizone kit is installed.
Maximum running time for domestic hot water operation.
Anti-recycling time.
Booster heater delay timer.
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
What is the desired comfort main LWT in cooling?
What is the desired eco main LWT in cooling?
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
--
--
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
What is the maximum desired LWT for main zone in cooling?
What is the mimimum desired LWT for main zone in cooling?
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
What is the mimimum desired LWT for add. zone in cooling?
--
--
DHW stratification
4P655201-1 - 2021.09
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*