15.3.7 Symptom: The pressure relief valve opens
Possible causes
Corrective action
The expansion vessel is broken
Replace the expansion vessel.
The water volume in the installation is
too high
Make sure that the water volume in the
installation is below the maximum
allowed value (see
and
"8.5.4 Changing the pre-pressure of
The water circuit head is too high
The water circuit head is the difference
in height between the indoor unit and
the highest point of the water circuit. If
the indoor unit is located at the highest
point of the installation, the installation
height is considered 0 m. The maximum
water circuit head is 10 m.
Check the installation requirements.
15.3.8 Symptom: The water pressure relief valve leaks
Possible causes
Corrective action
Dirt is blocking the water pressure relief
valve outlet
Check whether the pressure relief valve
works correctly by turning the red knob
on the valve counterclockwise:
▪
If you do NOT hear a clacking sound,
contact your dealer.
▪
If the water keeps running out of the
unit, close both the water inlet and
outlet shut-off valves first and then
contact your dealer.