8
|
Piping installation
Installer reference guide
101
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
NOTICE
To perform vacuum drying or a complete recharge of the outdoor unit’s internal
refrigerant piping it is necessary to activate the vacuum mode (see
deactivate the vacuum mode field setting"
103]) which will open required valves in
the refrigerant circuit so the vacuuming process or recharge of refrigerant can be
done properly.
▪
Before vacuum drying or recharging, activate field setting "vacuum mode".
▪
After finishing vacuum drying or recharging, deactivate field setting "vacuum
mode".
WARNING
Some sections of the refrigerant circuit may be isolated from other sections caused
by components with specific functions (e.g. valves). The refrigerant circuit therefore
features additional service ports for vacuuming, pressure relief or pressurizing the
circuit.
In case it is required to perform
brazing
on the unit, ensure that there is no pressure
remaining inside the unit. Internal pressures need to be released with ALL the service
ports indicated on the figures below opened. The location is depending on model
type.
Location of service ports:
c
a
b
a
Stop valve with service port (liquid)
b
Stop valve with service port (gas)
c
Internal service port
Typical workflow – Completely recharging refrigerant typically consists of the
following stages:
1
Determining how much refrigerant to charge.
2
Charging refrigerant.
3
Filling in the fluorinated greenhouse gases label, and fixing it to the inside of
the outdoor unit.
8.4.2 Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety precautions"
▪