175
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Heating
The unit will supply leaving water to the
heat emitters to heat up the room
according to normal logic.
▪
Space heating/cooling
=
On
, and
▪
Operation mode
=
Cooling
There is no room frost protection.
External room thermostat control
([C‑07]=1)
Under external room thermostat control, room frost protection is guaranteed by
the external room thermostat, provided that:
▪
[C.2]
Space heating/cooling
=
On
, and
▪
[9.5.1]
Emergency
=
Automatic
or
auto SH normal/DHW off
.
However, if [1.4.1]
Antifrost
is activated, limited frost protection by the unit is
possible.
In case of 1 leaving water temperature zone:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
The external room thermostat is
"Thermo OFF", and
▪
Outdoor temperature drops below
6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.
▪
Space heating/cooling
=
On
, and
▪
The external room thermostat is
"Thermo ON"
Room frost protection is guaranteed by
the normal logic.
In case of 2 leaving water temperature zones:
If...
Then...
▪
Space
heating/cooling
=
Off
,
and
▪
Outdoor ambient temperature drops
below 6°C
▪
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
▪
the temperature setpoint of the
leaving water will be lowered.