![Daikin Altherma 3 R F Installer'S Reference Manual Download Page 200](http://html.mh-extra.com/html/daikin/altherma-3-r-f/altherma-3-r-f_installers-reference-manual_501204200.webp)
11
|
Configuration
Installer reference guide
200
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
[9-0D]/[9-0E]=0
[9-0D]/[9-0E]=1/5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]/[9-0E]=2/6
[9-0D]/[9-0E]=3/7
[9-0D]/[9-0E]=4/8
a (kPa)
b (l/min)
a
External static pressure
b
Water flow rate
Pump outside range
When the pump operation function is disabled the pump will stop if the outdoor
temperature is higher than the value set by the
Space heating off
temperature
[4‑02] or if the outdoor temperature drops below the value set by
the
Space cooling off temperature
[F‑01]. When the pump operation is
enabled, the pump operation is possible at all outdoor temperatures.
#
Code
Description
[4.9]
[F-00]
Pump operation:
▪
0: Disabled if outdoor temperature is higher
than [4‑02] or lower than [F‑01] depending on
heating/cooling operation mode.
▪
1: Possible at all outdoor temperatures.
Increase around 0°C
Use this setting to compensate for possible heat losses of the building due to the
evaporation of melted ice or snow. (e.g. in cold region countries).
Summary of Contents for Altherma 3 R F
Page 309: ...13 13 ...
Page 310: ......
Page 311: ......
Page 312: ...4P655196 1 2021 09 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...