3/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
3.5
[0-01]
R/W
[9-05]~[9-06], step: 1°C
[2-0D]=0:
40°C
[2-0D]=1:
45°C
[2-0D]=2:
55°C
3.5
[0-02]
R/W
10~25°C, step: 1°C
15°C
3.5
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
└─
Cooling WD curve
3.6
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0D]=0:
18°C
[2-0D]=1:
5°C
[2-0D]=2:
18°C
3.6
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
3.6
[0-06]
R/W
25~43°C, step: 1°C
35°C
3.6
[0-07]
R/W
10~25°C, step: 1°C
20°C
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]
≠
2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
7°C
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C
Additional zone
3.A
[C-06]
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
└─
Delta T
3.B.1
[1-0C]
[2-0D]
≠
2:
R/W
[2-0D]=2:
R/O
[2-0D]
≠
2 (Radiator):
3~10°C, step: 1°C
5°C
[2-0D]=2 (Radiator):
8°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C
Space heating / cooling
└─
Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
35°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
Space heating / cooling
4.4
[7-02]
R/W
0: Single zone
1: Dual zone
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*5)
R/O (*6)
0: Reversible (*5)
1: Heating only (*6)
4.7
[9-0D]
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6 80% pump speed during sampling
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
2°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
55°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
Thermostat type
Delta T heating
Delta T cooling
Space heating OFF temp
Space cooling OFF temp
Number of zones
Pump operation mode
Unit type
Pump speed limitation
Pump outside range
Increase around 0°C
Overshoot
Room frost protection
Comfort setpoint
Eco setpoint
Reheat setpoint
Heat up mode
Activation
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*
4P655201-1 - 2021.09