![Daikin Altherma 3 R F Installer'S Reference Manual Download Page 235](http://html.mh-extra.com/html/daikin/altherma-3-r-f/altherma-3-r-f_installers-reference-manual_501204235.webp)
11
|
Configuration
Installer reference guide
235
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
2
On the user interface, go to [9.N]
Export MMI settings
.
3
Select
OK
.
4
Remove the USB memory stick and close the user interface
panel.
—
Bizone kit
Bizone kit installed
#
Code
Description
[9.P.1]
[E-0B]
Bizone kit installed
:
▪
0
No
: The system only has a main zone.
▪
1 N/A
▪
2
Yes
: A bizone kit is installed in order to add
an additional temperature zone.
Bizone kit system type
#
Code
Description
[9.P.2]
[E-0C]
Bizone system type
▪
0
Without hydraulic separator / no
direct pump
b
a
▪
1
With hydraulic separator / no
direct pump
b
a
c
▪
2
With hydraulic separator / with
direct pump
d
c
b
a
a
: Indoor unit;
b
: Mixing station;
c
: Hydraulic
separator;
d
: Direct pump
Summary of Contents for Altherma 3 R F