8
|
Configuration
Installer reference guide
130
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Setpoint range
For more information about
Setpoint range
, see
#
Code
Description
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1]
[9-05]
Heating minimum
: 15°C~37°C
[3.8.2]
[9-06]
Heating maximum
▪
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~60°C
▪
Else: 37°C~55°C
[3.8.3]
[9-07]
Cooling minimum
: 5°C~18°C
[3.8.4]
[9-08]
Cooling maximum
: 8°C~22°C
#
Code
Description
Leaving water temperature range for the main leaving water temperature zone (=
the leaving water temperature zone with the lowest leaving water temperature in
heating operation and the highest leaving water temperature in cooling
operation)
[2.8.1]
[9-01]
Heating minimum
:
▪
15°C~37°C
[2.8.2]
[9-00]
Heating maximum
:
▪
[2‑0C]=2 (emitter type main zone = radiator)
37°C~70°C
▪
Otherwise: 37°C~55°C
[2.8.3]
[9-02]
Cooling minimum
:
▪
5°C~18°C
[2.8.4]
[9-03]
Cooling maximum
:
▪
18°C~22°C
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
117].
#
Code
Description
[3.9]
N/A
Control
:
▪
Leaving water
if the control type of the
main zone is
Leaving water
.
▪
External room thermostat
if the control
type of the main zone is:
-
External room thermostat
,or
-
Room thermostat
.