7
|
Installation
Installer reference guide
97
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
7.6.16 To connect the power consumption digital inputs
1
Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
X1M
X2M
A8P
X5M
1 2 3 4 5
X801M
S6S
S7S
S8S
S9S
a
a
Installation of EKRP1AHTA is required.
2
Fix the cable with cable ties to the cable tie mountings.
7.6.17 To connect the safety thermostat (normally closed contact)
1
Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
X1M
X2M
X5M
9 10
2
Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat according to the applicable
legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, we
recommend the following:
▪
The safety thermostat is automatically resettable.
▪
The safety thermostat has a maximum temperature variation rate of 2°C/min.
▪
There is a minimum distance of 2 m between the safety thermostat and the
3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat after it is installed. Without configuration,
the indoor unit will ignore the safety thermostat contact.