8
|
Configuration
Installer reference guide
123
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
#
Code
Description
[2.8.1]
[9-01]
Heating minimum
:
▪
15°C~37°C
[2.8.2]
[9-00]
Heating maximum
:
▪
[2‑0C]=2 (emitter type main zone = radiator)
37°C~70°C
▪
Otherwise: 37°C~55°C
[2.8.3]
[9-02]
Cooling minimum
:
▪
5°C~18°C
[2.8.4]
[9-03]
Cooling maximum
:
▪
18°C~22°C
Control
Define how the operation of the unit is controlled.
Control
In this control...
Leaving water
Unit operation is decided based on the leaving water
temperature regardless the actual room temperature
and/or heating or cooling demand of the room.
External room
thermostat
Unit operation is decided by the external thermostat or
equivalent (e.g. heat pump convector).
Room thermostat
Unit operation is decided based on the ambient
temperature of the user interface used as a room
thermostat.
#
Code
Description
[2.9]
[C‑07]
▪
0:
Leaving water
▪
1:
External room thermostat
▪
2:
Room thermostat
Thermostat type
Only applicable in external room thermostat control.
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if [C.2]
Space heating/cooling
=
On
.