5
|
Application guidelines
Installer reference guide
31
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Benefits
▪
Cooling.
Heat pump convectors provide, besides heating capacity, also excellent
cooling capacity.
▪
Efficiency
. Underfloor heating has the best performance with the heat pump
system.
▪
Comfort.
The combination of the two heat emitter types provides:
-
The excellent heating comfort of the underfloor heating
-
The excellent cooling comfort of the heat pump convectors
5.2.2 Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the design leaving
water temperature of all heat emitters is the same, you do NOT need a mixing
valve station (cost effective).
Example:
If the heat pump system is used to heat up one floor where all the rooms
have the same heat emitters.
Underfloor heating or radiators – Thermostatic valves
If you are heating up rooms with underfloor heating or radiators, a very common
way is to control the temperature of the main room by using a thermostat (this can
either be the user interface or an external room thermostat), while the other
rooms are controlled by so-called thermostatic valves, which open or close
depending on the room temperature.
Setup
A
T
B
C
a
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
User interface used as room thermostat
▪
The underfloor heating of the main room is directly connected to the indoor unit.
▪
The room temperature of the main room is controlled by the user interface used
as a room thermostat (optional equipment BRC1H).
▪
A thermostatic valve is installed before the underfloor heating in each of the
other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source.
Example: Fireplaces.